Skip to main content
Skip table of contents

Querprofil Freileitung

Die Definition eines Querprofils einer Freileitung erfolgt über die Definition der verschiedenen Masten eines Masttyps. Die Definition erfolgt im Modeller “Powerpole”.

Beispiel:

CODE
<poleconfig name="D29" info="D29 Strommastkonfiguration">
  <container name="poles">
    <pole name="TD" kind="D29" type="Tragmast" anglemin="180.0" anglemax="180.0" height="44.90" widthl="14.50" widthr="14.50" model="OPP_D29_TD_MAST"  top="OPP_D29_TD_SPITZE" id="{0AFF9730-8FA3-451C-9645-FB01F46A676E}">
      <polesections>
        <polesection order="1" model="OPP_D29_TD_SCHUSS1" id="{BA28DE94-3881-48B2-9E7C-8E17883A800A}"/>
        <polesection order="2" model="OPP_D29_TD_SCHUSS2" id="{F90BD68A-59A4-4808-B83B-B8BC6B399A87}"/>
        <polesection order="3" model="OPP_D29_TD_SCHUSS3" id="{C48BB027-AA1B-43AC-AA5E-76E4FF1D1E3E}"/>
        <polesection order="4" model="OPP_D29_TD_SCHUSS4" id="{99DC11D5-BCA0-47F3-9930-50273D37B8DB}"/>
      </polesections>
      <container name="traverses">
        <traverse z="0.00" model="OPP_D29_TD_TRAVERSE_II" id="{4CE05D5A-74F5-46A0-89D1-620D74EEDF11}">
          <container name="linepoints">
            <linepoint t="-14.5" line="line_1" id="{D204929B-D355-4E7C-A723-EA9BB06273A6}"/>
            <linepoint t="-8.2" line="line_1" id="{5419800C-CE49-4F7B-96FB-62EA294A6041}"/>
            <linepoint t="8.2" line="line_1"id="{F82DAA68-E65F-47B6-B987-C03EE8E297DB}"/>
            <linepoint t="14.5" line="line_1"id="{87AC0F53-7BF6-4BEC-925F-2A28581EACE0}"/>
          </container>
        </traverse>
        <traverse z="10.00" model="OPP_D29_TD_TRAVERSE_I"id="{2A2EBC6D-E0EC-4669-B571-5AFA6278239E}">
          <container name="linepoints">
            <linepoint t="-11.3" line="line_1" id="{AF35844F-41FC-428E-B62B-1F7CB6229637}"/>
            <linepoint t="11.3" line="line_1" id="{9F73A83E-5784-4B1E-8091-A477ABEFBD68}"/>
          </container>
        </traverse>
      </container>
      <earth>
        <container name="linepoints" z="21.9">
            <linepoint t="0" line="earth_1" id="{93435760-EB42-4EE6-AA6C-07FC09AA5016}"/>
        </container>
        <container name="linepoints" z="12.4">
            <linepoint t="0" line="luftkabel" air="true" earth="false" id="{55D4A69D-D171-47CF-BE42-6BD0AA88D3A1}"/>
        </container>
        <container name="linepoints" z="3.1">
            <linepoint t="0" line="luftkabel" air="true" earth="false" id="{7DD6CCD0-A436-4372-A12B-0386D8C6143C}"/>
        </container>
      </earth>
      <container name="variants">
        <variant name="18,5" height="23.0" model="OPP_D29_TD_18_50" basement="OPP_D29_TD_18_50_FUND" id="{F6E60C06-0A85-4168-89E1-88DC8E46DF29}">
          <polesections>
              <polesection order="1" model="OPP_D29_TD_SCHUSS5" id="{31BC27DD-6880-418F-B508-DCF9023E725F}"/>
              <polesection order="2" model="OPP_D29_TD_SCHUSS6" id="{7EE822C7-0CF4-45C0-BD4F-F8854985F41A}"/>
          </polesections>
        </variant>
        <variant name="24,5" height="29.0" model="OPP_D29_TD_24_50" basement="OPP_D29_TD_24_50_FUND" id="{023E32CF-D388-450B-894B-D425E90D75DD}"/>
      </container>
    </pole>
     <pole name="WA1" kind="D29" type="Abspannmast" anglemin="160.0" anglemax="180.0" height="49.00" widthl="14.60" widthr="14.60" model="OPP_D29_WA1(3)_MAST" top="OPP_D29_WA1_SPITZE" id="{CF21F811-FBAC-4049-A4D4-E218C1AFA47D}">
       <container name="traverses">
         <traverse z="0" model="OPP_D29_WA1_TRAVERSE_II" id="{88C9B984-361C-465E-8C65-15ED780AC8D9}">
           <container name="linepoints">
             <linepoint t="-14.6" line="line_1" id="{643D4ECC-139C-4730-BD3E-99CEB4EB16CC}"/>
             <linepoint t="-8.2" line="line_1" id="{5CA7E82D-7F13-4AB3-9792-4C5AF8F4FC3F}"/>
             <linepoint t="8.2" line="line_1" id="{14F9A833-6DA4-40EF-AD97-F5EFE0B6BD8B}"/>
             <linepoint t="14.6" line="line_1" id="{D33C7EF4-40FC-42DE-AF59-2C4C0E424E9B}"/>
           </container>
         </traverse>
         <traverse z="10" model="OPP_D29_WA1_TRAVERSE_I" id="{60464764-2689-44CB-B2DE-86C54C953479}">
           <container name="linepoints">
             <linepoint t="-11.4" line="line_1" id="{2507B8E7-4826-4C3E-8461-1C55C7BCEB31}"/>
             <linepoint t="11.4" line="line_1" id="{49D5DA22-C5BA-4BC7-A295-0D8293A9BF34}"/>
           </container>
         </traverse>
       </container>
       <earth>
         <container name="linepoints" z="26">
           <linepoint t="0" line="earth_1" id="{0AF5BD7B-87B5-4959-BBC7-8985B33F118C}"/>
         </container>
         <container name="linepoints" z="12.5">
           <linepoint t="0" line="luftkabel" air="true" earth="false" id="{DC43F946-C424-4DB2-8DF5-CB4CB76574EE}"/>
         </container>
         <container name="linepoints" z="3.3">
           <linepoint t="0" line="luftkabel" air="true" earth="false" id="{D3136D6E-2358-4C1A-9540-B305E70CFA12}"/>
         </container>
       </earth>
       <container name="variants">
         <variant name="23" height="23.0" model="OPP_D29_WA1(3)_23" basement="OPP_D29_WA1(3)_23_FUND" id="{DB90075D-469C-4E31-A07D-65122AE1981E}"/>
         <variant name="26" height="26.0" model="OPP_D29_WA1(3)_26" basement="OPP_D29_WA1(3)_26_FUND" id="{6256CD53-1922-4981-9D5A-EADB512FBF78}"/>
       </container>
    </pole>
  </container>
  <container name="linesets">
    <lineset name="std" info="Standard">
      <line name="line_1" isotrag="iso_324" isoline="isoline_324" line="seil_560_50_4" id="{EEBF1C07-3224-4777-B5A4-99C4888D0CB1}"/>
      <line name="earth_1" line="seil_265_35" id="{1038BF2F-E5AC-4F45-AFEB-F39B6D81137F}"/>
      <line name="luftkabel" line="seil_265_35" id="{339DBAEE-8A8D-4717-9BF3-DCFEEE5E6B89}"/>
    </lineset>
  </container>
  <container name="sets">
    <set info="2x3x4 Al/St 560/50, 1x Al/St 265/35" name="std" lineset="std" />
  </container>
</poleconfig>

Mit folgenden Erklärungen:

Allgemein

Schalter

Erklärung

name

Entspricht jeweils der ID des entsprechenden Elements. Im Bereich pole und variants entspricht dies auch dem angezeigten Namen in KorFin®.

info

Information zum entsprechenden Element. Wird großteils auch in KorFin® angezeigt.

poleconfig

Fasst verschiedene Maste zu einer Konfiguration zusammen. In dieser Konfiguration werden die Seile von einem Mast zum nächsten geführt. Die Konfiguration besteht aus mehreren Masten (container poles), Seilkonfigurationen (container linesets) und Auswahlsets (container sets).

pole

Definiert einen Mast innerhalb des container poles.

lineset

Definiert die Kombination der verwendeten Seile samt Isolatoren für Abspann- und Tragmaste. Die definierten Seile werden in den linepoints der Traversen eines Mastes verwendet.

set

Definiert, welches lineset verwendet wird.

  • name ist die ID des sets,

  • info gibt den sichtbaren Namen in der Querprofilmarke an,

  • lineset definiert das zu verwendende lineset.

id

Gibt die GUID des einzelnen Bauteils bzw. Objekts innerhalb des Mastes an. Diese muss eindeutig über das gesamte System sein.

Mast

Schalter

Erklärung

name

Entspricht sowohl der ID als auch dem angezeigten Namen des Mastes.

type

Definition des Mastes: Tragmast oder Abspannmast.

anglemin/anglemax

Definiert die Verwendung des Mastes bezüglich des Winkels in der Automatik.

height

Höhe des Mastes.

widthl/widthr

Breite des Mastes links und rechts.

model

Zu verwendendes Objekt aus einer KorFin®-Ressource zur geometrischen Darstellung des Mastes.

top

Zu verwendendes Modell für die Mastspitze.

container traverses

Definiert die Traversen des Mastes mit Abstand jeweils zur letzten Traverse. Enthält ebenfalls die Definition der Aufhängepunkte der Seile und das jeweils zu verwendende Seil im Bereich linepoints.

container variants

Definiert die verschiedenen Höhenstufen der Maste.

earth

Definiert verschiedene Erdseile. Innerhalb der linepoints erfolgt über die Schalter air=true/false oder earth=true/false die Definition des Kabels als Erdkabel oder Luftkabel. Ausstattungen auf Erdkabel (z.B. Vogelschutzmarker) werden nur auf Erdkabeln abgesetzt, nicht auf Luftkabeln.

polesections

Definiert die einzelnen Schüsse eines Mastes bzw. einer Mastvariante.

Weitere Informationen:

Bauteilinformationen für Freileitungsmastbauteile

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.